Features
– Compact and lightweight.
– The cam can be detachable with levers on.
– Split range available.
– High endurance for vibration.
– Easy zero-span adjustment.
– Easy maintenance.
– 4 to 20 mA feedback signal function available (optional).
Specification
Specs |
Standard |
Option |
Input Signal |
4 to 20 mADC / 250Ω |
|
Supply air pressure |
0.14 to 0.7 MPa |
|
Stroke |
10 to 100 mm (option: 3 to 10 mm) / 60 to 90° |
|
Air connection |
Rc1/4
(Gauge Rc1/8) |
NPT1/4
(Gauge NPT1/8) |
Power Connection |
G1/2 |
NPT1/2 |
Pressure gauge |
0 to 0.2 MPa
0 to 0.4 MPa
0 to 1.0 MPa |
|
Enclosure protection level |
IP65 (IEC529-1989) |
|
Construction |
Non-explosion proof
Flameproof: Ex d II BT6
Intrinsically safe: EEx i aIIC T4, T5, T6 |
|
Cam |
Linear |
Non-linear |
Ambient temperature |
Standard: -20 to 83 ℃
(Flameproof: -20 to 60 ℃)
Low Temp. -50 to 60 ℃
High Temp. 0 to 100 ℃ |
|
Material |
Body: Aluminum Diecasting (Special Anodize)
Standard cover: Aluminum Diecasting (Special Anodize) |
|
Weight |
Single acting: Approx. 2.2 Kgs
Double acting: Approx. 2.3 Kgs |
|
Specification
Specs |
Single acting |
Double acting |
Linearity |
±1.5 % |
Hysteresis |
1.0 % |
Repeatability |
0.5 % |
Sensitivity |
0.5 % |
range of supply air |
0.3 % /0.01 MPa |
resistance against vibration |
1 % / 1 G |
Air consumption
(Nl/min) |
5 / 0.14 MPa
at Output pressure 50 % |
11/0.4MPa
at Output pressure 75 % |
Max Cv.
(Nl/min) |
180 to 200 Nl / min. / 0.4 MPa |
Attention for usage of pneumatic instruments
* Clean and dry air (dew point -30 or below) is required.
* Air filter 5μm or smaller is required.
All specifications are subject to change without prior notice.
All figures are effected by the valve/actuators.