Specification
Item |
TE100
(with a junction box) |
TE200
(without a junction box) |
Supply air pressure | 140kPa(1.4kgf/cm2) |
Output pressure | 20~100kPa(0.2~1kgf/cm2) |
Input signal | 4~20mADC |
Accuracy | ±0.5%
(Linearity: ±0.2%, Hysteresis: ±0.2%, Repeatability: ±0.1%) |
Output air capacity | 40Nl/min (approx.) |
Air consumption | 3Nl/min(with a Mini-Set integrated,4Nl/min) |
Operating temperature limit | Ambient temperature Standard: -20 to 80C°
Explosion proof (ExdIIBT6): -20 to 60C° | Ambient temperature Standard: -20 to 80C°
Explosion proof (ExdIIBT6): -20 to 60C° |
Air connection |
Standard: Rc 1/4 (Gauge Rc 1/8)
Option: NPT 1/4 (Gauge NPT 1/8) female |
Electrical wire connection | Standard: G1/2, Option: NPT1/2 female |
Structures | Non-explosion proof
frameproof : ExdIIBT6—JIS — | Non-explosion proof |
Weight Approx | 3.5lbs (1.8kgs)(3.9lbs with a Mini-Set integrated) | 2.8lbs (1.3kgs)(3.2lbs with a Mini-Set integrated) |
Major material | Aluminum Diecastings (ADC12)
|
(Warning): The above contents are subject to change without notice.
Pneumatic instrument / precautions
*Clean dry air (dew point – 30℃ or below) is required.
*Air filter (mesh 5μm or less) is required.
How to check serial number
We have a database, which can specify model from serial number.Please let us know the Serial Number written on the plate.